SZL Series Hot Water Boiler | |||||||||
Boiler Type Item |
SZL4.2-1.0/ 95/70-AII |
SZL5.6-1.0/95 /70-AII |
SZL7.0-1.0/ 115/70-AII |
SZL10.5-1.25/ 150/90-AII |
SZL14-1.25/ 150/90-AII |
||||
Rated Thermal Power | Mw | 4.2 | 5.6 | 7.0 | 10.5 | 14 | |||
Rated Pressure | MPa | 1.0 | 1.0 | 1.0 | 1.25 | 1.25 | |||
Outlet Water Temperature | ºC | 95 | 95 | 115 | 150 | 150 | |||
Returned Water Temperature |
ºC | 70 | 70 | 70 | 90 | 90 | |||
Thermal Efficiency |
% | 78 | 79.6 | 78.7 | 80.8 | 81.7 | |||
Boiler Heating Area |
M² | 154 | 175 | 234 | 471 | 578 | |||
Grate Area | M² | 7.15 | 8.6 | 11.72 | 16.4 | 18.9 | |||
Heating Area | M² | 36,000 | 48,000 | 60,000 | 90,000 | 120,000 | |||
Fuel | Coal | AII | |||||||
Consumption | Kg/L | 900 | 1280 | 1450 | 2460 | 3240 | |||
Water Tube Diameter | MM | PN1.6/DN150 | PN1.6/DN200 | PN1.6/DN150 | PN1.6/DN200 | PN1.6/DN200 | |||
Maximum Transportation Size (L * W * H) | M | 7.62×3.27 ×3.46 |
8.82×3.34 ×3.46 |
7.78×3.38 ×3.53 8×3.5 ×2.7 |
9.05×3.35 ×3.69 |
10.59×3.35 ×3.69 |
|||
Maximum Transportation Weight | T | 31 | 45 | 28/27 | 24 | 27 | |||
Boiler Weight | T | 36 | 53 | 95.3 | 108 | 116 | |||
The Installed Dimension | M | 8.4×4.9 ×3.92 |
9.38×5.33 ×3.86 |
9.8×5.2 ×6 |
12.3×5.3 ×7.2 |
14.22×5.3 ×8.04 |